Call us on 01634 729 690
How to remove and refit a Plate Recuperator Removable Drain Tray
Before You Begin
- Select Maintenance Mode and allow the fans to stop fully.
- Isolate the fan system electrically and apply lock-off/tag-out if required.
- Have absorbent materials ready for residual condensate.
- Confirm the plate pack and drain tray area can be accessed safely before removal.
Quick Overview
- Isolate the AHU and access the plate recuperator section.
- Disconnect the drain and remove the retaining panel if fitted.
- Remove, inspect and clean the recuperator drain tray.
- Refit the tray, reconnect the drain and verify operation after restart.
Keep This Guide On Hand
This guide explains the safe removal, cleaning, inspection and refitting of the removable stainless-steel drain tray beneath the plate recuperator section. It supports drainage integrity, hygiene compliance and downstream component protection.
Video guide | 9 minutes 25 Seconds | Booklet included
Written Guide Overview
This written summary mirrors the booklet and gives users a quick reference to the key steps show in the video.
|
1
|
Isolate the unit, open the plate recuperator section, and disconnect the drain hose while capturing any residual condensate. |
|
2
|
Remove the retaining panel if fitted, then withdraw the tray fully along the guide rails while keeping it level. |
|
3
|
Inspect the tray for corrosion, distortion and hygiene issues, clean it thoroughly, and inspect the plate recuperator area and drain spigot. |
|
4
|
Refit the tray with the correct fall, reconnect the drain, reinstall the panel, restart the unit and verify that condensate drains freely with no leakage or carryover. |
What this guide covers
- Isolation and safe access to the plate heat exchanger section.
- Disconnecting the drain and removing the retaining panel.
- Withdrawing the drain tray without spillage.
- Structural and hygiene inspection of the tray.
- Refitting the tray with correct fall and hose connection.
- Restart and drainage verification.
Need further assitance?
If the portal does not load, re-check the internet connection, QR scan and 18-digit reference number. If access still fails, contact ECE support and quote the unit’s reference number. You can reach our team on 01634 729 690 or sales@eceuk.com.