How to remove and refit a Cooling Coil Removable Drain Tray

Call us on 01634 729 690

Before You Begin
  • Select Maintenance Mode and allow the fans to stop fully.
  • Isolate the fan system electrically and apply lock-off/tag-out if required.
  • Have absorbent materials ready for residual condensate.
  • Confirm the tray and cooling coil area are accessible before disconnecting drainage.
Quick Overview
  • Isolate the unit and access the cooling coil section safely.
  • Disconnect the drain and remove any internal retaining panel.
  • Withdraw, inspect and clean the removable tray.
  • Refit the tray, reconnect the drain and verify operation after restart.
Keep This Guide On Hand

This guide explains the safe removal, cleaning, inspection and refitting of the stainless-steel removable drain tray beneath the cooling coil section. It is intended to help maintain correct drainage, hygiene performance and leak-free operation.

Video guide | 7 minutes 22 Seconds | Booklet included

Download Guide

Written Guide Overview

This written summary mirrors the booklet and gives users a quick reference to the key steps show in the video.

1
Isolate the unit, open the cooling coil section, and disconnect the drain connection while controlling any residual condensate.
2
Remove the internal retaining panel if fitted, then withdraw the drain tray evenly along its guide rails.
3
Inspect and clean the tray, clear the outlet, and check surrounding components and seals before refitting.
4
Reinstall the tray and panel, reconnect the drain, close the unit, restart the system, and verify free condensate flow with no leaks or carryover.
What this guide covers
  • Maintenance Mode and electrical isolation.
  • Accessing the cooling coil section.
  • Disconnecting the drain connection safely.
  • Removing the tray and any internal panel.
  • Inspection, cleaning and drain outlet checks.
  • Refit, restart and post-restart drainage verification.

Need further assitance?

If the portal does not load, re-check the internet connection, QR scan and 18-digit reference number. If access still fails, contact ECE support and quote the unit’s reference number. You can reach our team on 01634 729 690 or sales@eceuk.com.

Make a design enquiry

Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.